Product Name |
Alarm Definition |
Processing Strategies |
A00-Grid AC over voltage |
The grid voltage exceeds the allowable range |
1. If the alarm occurs occasionally, it means the grid abnormal, the inverter can automatically recover to normal operating status after the grid return normal.
2. If the alarm occurs repeatedly and it can automatically recover, need to contact local electric power department to get permission to modify the inverter grid protection parameters with APP.
3. If the alarm occurs repeatedly for a long time, please confirm
1) If the output breaker is closed?
2)If the output terminal is ok?
3)If grid is power off?
4)If the output cable follow the User Manual guidance? |
A01-Grid AC under voltage |
A02-Grid AC absent |
The grid voltage is 0 volt |
A03-Grid AC over frequency |
The grid frequency exceeds the allowable range |
A04-Grid AC under frequency |
B00-PV DC over voltage |
PV module input voltage is higher than the allowable range |
Please measure the PV input voltage with multimeter, and compare it with the “Max input voltage” written the inverter lable. If PV input voltage is larger than “Max input voltage”, then reduce the PV module quantity. |
B01-PV insulation abnormal |
The insulation resistance against the ground is lower than the allowable range |
1. If the alarm occurs occasionally, it may be caused by external circuit, the inverter can automatically recover to normal operating status after the fault is cleared.
2. If the alarm occurs repeatedly or lasts a long time, please follow below steps:
1) Check if the output cable is stable.
2) Plug the PV strings one by one to find the abnormal PV strings. Please check if the insulation resistance against the ground of PV strings is too low, or the cable is broken, or cable connection incorrectly. |
B02-Leakage current abnormal |
The residual current is high. |
1. If the alarm occurs occasionally, it may be caused by external circuit, the inverter can automatically recover to normal operating status after the fault is cleared.
2. If the alarm occurs repeatedly or lasts a long time, please follow below steps:
1) Check if the output cable is stable.
2) Plug the PV strings one by one to find the abnormal PV strings. Please check if the insulation resistance against the ground of PV strings is too low, or the cable is broken, or cable connection incorrectly. |
B03-PV string abnormal |
PV strings have been shielded for a long time or PV strings is abnormal |
1. Check whether the PV string is shielded.
2. If the PV string is clean and not shielded, check if the PV modules are aging or deteriorated, or if cable/terminal is abnormal. |
B04-PV DC under voltage |
PV modules input voltage is under default protection value. |
1. If alarm occur during sunlight weak(At morning or dawn, raining or ), it’s normal and no action is needed.
2. If not, please check if there is PV module connection short circuit. |
A06-Grid voltage unbalanced |
The grid voltage unbalanced exceeds the allowable range |
1. If the alarm occurs occasionally, it means the grid abnormal, the inverter can automatically recover to normal operating status after the grid return normal.
2. If the alarm occurs repeatedly and it can automatically recover, need to contact local electric power department to get permission to modify the inverter grid protection parameters with APP.
3. If the alarm occurs repeatedly for a long time, please confirm
1) If the output breaker is closed?
2)If the output terminal is ok?
3)If grid is power off?
4)If the output cable follow the User Manual guidance? |
C02-Output DC over current |
Grid DC component current is higher than than the allowable range |
1. If the alarm occurs occasionally, it’s caused by grid voltage abnormal temporarily, the inverter can automatically recover to normal operating status, no action is needed.
2. If the alarm occurs repeatedly or lasts a long time, please contact customer service center. |
C03-Inverter relay abnormal |
Internal relay abnormal |
1. If the alarm occurs occasionally, it’s caused by grid voltage abnormal temporarily, the inverter can automatically recover to normal operating status, no action is needed.
2. If the alarm occurs repeatedly or lasts a long time, please check if output neutral line and fire line reverse connection. If not, please contact customer service center. |
C05-Inverter over temperature |
Internal temperature is higher than than the allowable range |
1. If the alarm occurs occasionally, the inverter can automatically recover to normal operating status, no action is needed.
2. If the alarm occurs repeatedly or lasts a long time, please check if the installation site is direct sunlight, ventilation is good, the ambient temperature is too high. If not, please contact cusomer service center. |
C06-Leakage current HCT abnormal |
Residual current device test is failure |
1. If the alarm occurs occasionally, it may be caused by external circuit abnormal, the inverter can automatically recover to normal operating status after fault is cleared.
2. If the alarm occurs repeatedly or lasts a long time, please check if the insulation resistance against the ground of PV strings is too low, or the cable is broken, or cable connection incorrectly. |
B07-PV string reverse |
The polar of PV strings is reversed. |
Check whether the cables of PV strings are correctly connected. If they are connected reversely, reconnect the cables. |
C08-Fan lock |
Fan abnormal |
1. If the alarm occurs occasionally, please restart inverter.
2. If the alarm occurs repeatedly or lasts a long time, please check if fan is blocked. If not, please contact customer service center. |